|
Harmonic Filter Bank Tuning -
Tuned & De-Tuned Banks
When
designing or applying a harmonic filter, the question
that comes to the mind of many engineers is; What harmonic
or frequency should the harmonic filter bank be tuned
too? i.e., 4.2 (de-tuned), 4.8 (partially de-tuned)
or 5.0 (tuned). To answer this question, the engineer
should know why the filters are being installed in the
first place. Harmonic filters are generally installed
to achieve one of the following objectives:
1.
Capacitors are required to improve power factor, and
possible system interaction may occur with the installation
of a plain capacitor bank.
2.
Permissible distortion limits of the local utility or
IEEE-519 are exceeded, and filters are required to reduce
them.
3.
A combination of 1 and 2 above, whereby capacitors are
required to improve power factor and with the addition
of the capacitors, permissible distortion limits are
exceeded.

Figure
1 - Typical
Industrial System
This
technical article discusses the proper type of filter
for each of the above applications and provides design
and performance issues related to tuned, de-tuned and
partially de-tuned harmonic filter banks. Consult NEPSI
for other bulletins that may assist you in the selection
and application of harmonic filter banks and capacitor
banks.
Background
- Tuning
Figure 2 shows
a typical frequency scan for a 4.2th, 4.8th, and 5th
harmonic filter when placed on a system as shown in
Figure 1. The frequency scan shows the apparent impedance
as a function of frequency as seen by an injected current
at the location shown in Figure 1. This injected current
is usually termed a harmonic current source and usually
consist of non-linear loads, such as variable speed
drives, switch mode power supplies, and welders. The
scan shows how the tuning point effects the apparent
impedance, mainly in the area of tuning, near the 5th
harmonic. A blow up of this tuning area is shown in
Figure 3

Figure 2 -
Filter Tuning Point Comparison
The
impedance scan is useful since it gives an indication
of the filter characteristics and how it interacts with
the system that it is being applied on. For example,
the filter tuning point can be determined by looking
at the minimum impedance, or "notch". In addition,
the anti-resonant point, the peak just below the tuning
point, can also be determined. The anti-resonant point
always exists below the tuned frequency of a filter,
and significant harmonics at this frequency should be
avoided. When applying de-tuned filters below the 4.2th,
careful consideration should be given to possible resonant
concerns at the 3rd harmonic.
To
put reality into the scans, one may say that one per
unit of current injected into one per unit impedance,
produces one per unit voltage. In looking at Figure
3, one per unit current injected into the system at
the fifth harmonic will produce those voltage levels
shown on the ordinate of Figure 3. That is the 4.2th
will produce a 5th harmonic voltage of 0.275 per unit.
The 4.8th will produce a 5th harmonic voltage of 0.072
per unit and the 5th filter a voltage of 0.006 per unit.
With respect to filtering, the 5th harmonic filter perform
the best of the three filters, since the lowest harmonic
voltage is produced for a one per unit injection.

Figure 3 -
Close up of tuning point
Filter
Performance
From the above
discussion, it is apparent that tuning has a definite
effect on filter performance and system interaction.
The question of whether to tune, de-tune or partially
de-tune is a question of economics, objective of filtering,
and negative system interaction. A tuned filter cost
more than a partially de-tuned filter, and likewise
a partially de-tuned filter cost more than a de-tuned
filter. The reason the for the cost difference, is the
duty requirements for both the capacitors and the reactors.
For
example, the filter currents for various tuning points
for the typical system in Figure 1 are illustrated in
Table 1. The Table is based on 100 amps of 5th harmonic
current injected from the non linear load. This current
may flow back to the utility or into the harmonic filter,
and is dependent upon the filter impedance and system
impedance at the 5th harmonic. Table 1 shows that the
5th harmonic filter will absorb most of the harmonic
current and that very little will be absorbed by the
utility. As a result, the fifth harmonic filter would
require a 5th harmonic current rating of 99 Amps. The
4.8th harmonic filter absorbs less, and would require
a 5th harmonic current rating of 70 Amps. The 4.2th
harmonic filter absorbs very little harmonic current
(20 Amps), while the utility and the remaining system
absorbs the remaining 80 Amps. The conclusion here is
simple, tuning the filter closer to the fifth harmonics
requires higher reactor current ratings, (and also capacitor
voltage ratings) which result in higher filter bank
cost.
|
Table
1 -
Filter Performance
|
|
Filter
Type
|
Filter Current
(amps)
|
Utility System
(amps)
|
|
5th
|
99
|
1
|
|
4.8th
|
70
|
30
|
|
4.2nd
|
20
|
80
|
Conclusion
The choice of
tuning frequency is based on the objective of the
harmonic filter and economics. The following guidelines
may assist the engineer in determining the proper
type (tuning frequency) of filter.
De-tuned
Filters (Tuning between 4.0 and 4.4)
If harmonic
filters are being considered only for the purpose of
power factor correction, then a de-tuned filter bank
is the best choice. This filter will do little for removing
any harmonic distortion present on the system but will
allow the installation of a large capacitor bank without
any adverse system interactions. De-tuned filter banks
are less costly an are more reliable than partially
de-tuned and tuned filter banks. The anti-resonant frequency
should be considered to assure that it does not fall
near the 3rd harmonic.
Partially
Tuned Filter (Tuning between 4.4 and 4.8)
In some situations,
a filter (or capacitor bank) is required to improve
power factor, and at the same time distortion limits
are exceeded. In this situation, a partially tuned filter
bank is usually the best choice. A partially tuned bank
offers less risk and is typically less costly than a
tuned filter bank.
Tuned
Filters (Tuning between 4.8 and 5.0)
If harmonic
filters are being considered only for the purpose of
reducing the harmonic distortion to acceptable limits,
then a tuned filter bank should be considered. A tuned
filter bank will require the least amount of kvar to
bring the distortion down within limits, but will require
the highest level of engineering design. It has the
highest level of risk, since it will draw most of the
harmonics present on the industrial system and local
utility system. Harmonic load growth should be considered,
along with ambient voltage distortion level. The application
of this type of filter should include a detailed harmonic
analysis by the manufacturer.
Other
Filter Types
Fifth
harmonic filters have been the main topic of discussion.
Other types of filters are some times required, i.e.,
5th, 7th, 11th filter banks. Or 5th, 7th, 11th and 13th
high pass. These filters are designed with optimization
and with specific current distortion limits in mind.
They are more costly then simple tuned filter banks
but are much more effective in reducing the system distortion.
They are generally applied to systems with large amounts
of non-linear load.
|