The incoming compartment is typically provided with 200 amp bushing wells, stainless steel parking stands, and a hinged Lexan Barrier to allow for viewing and removal of capacitor bank fuses.

  Three-Line Diagrams
  Pad Mounted Capacitor BankThree-line diagram in Autocad Format Autocad 2000 Format
  DXF Drawing Exchange Format
 

 

 
  Elevation Drawings
  Pad Mounted Capacitor Bank Elevation Drawing in Autocad Format Autocad 2000 Format
  DXF Drawing Exchange Format

Feel Free to Start With Above Drawing Files For Development of Specifications

 

The live-front capacitor compartment allows for maintenance and removal of vacuum switches, CPT and double bushing capacitors.

The control compartment is segregated from the incoming compartment and the capacitor compartment. Controls are built custom to meet customer requirements. Above pictures shows a Fisher Pierce 4400 AutoCap Capacitor Controller mounted on a swing-out panel.

  MV-DFCB, Medium Voltage Pad-Mounted Dead-Front Capacitor Banks
  Microsoft Word Format
  Rich Text Format
 

 

 
  SCADA System For Automatic Capacitor Banks
  Microsoft Word Format
  Rich Text Format
 
If the above specifications do not meet your requirements, NEPSI will work with you to develop a specification that conforms to your specific application.
  Pricing,Weights & Dimensions
 

HTML
Format

MV-DFCB Budgetary Cost, Dimensions, and Weights

Costs, weights, and dimensions are for budgetary and planning purposes only. For competitive pricing and exact weight and dimensions, contact NEPSI.


Medium Voltage Pad-Mounted
Capacitor Banks

Northeast Power System's (NEPSI's) medium voltage pad-mounted capacitor banks are designed for application on utility distribution systems in areas that are accessible to the public. These capacitor banks are compact, low profile, and are painted "pad-mount" green to blend in with the surrounding environment. They are designed, constructed, and tested to meet or exceed ANSI C57.12.28 Pad-Mount Enclosure Standard.

Product Scope
  • Single Stage and two stage capacitor banks from 600 kvar to 3000 kvar in voltages to 34.5kV.
  • Banks can be customized to meet utility requirements or existing designs.
  • Automatic control of power factor from light load conditions through heavy load conditions.
  • Standardized low-profile, compact design comes fully assembled and ready for interconnection.
  • Easy to install and maintain on underground distribution system using standard 200 amp and 600 amp separable connectors.
  • Provides loss reduction and voltage support on systems largely composed of cable.
  • Meets requirements of ANSI C57.12.28 and the original Western Underground Committee Guide 2.13 for enclosure integrity.
Standard Features

Enclosure
Single self-supporting unit designed to meet or exceed the requirements of ANSI C57.12.28 for enclosure integrity. Enclosure is constructed of 11 gauge galvanneal steel and is painted Munsell Green No. 7GY3.29/1.5. The base of the enclosure, as well as the capacitor and switch supports consists of C4 x 5.4 structural steel channel for rigidity and skidding into place. The roof is cross-kinked for added strength and water shedding. Removable lifting plates are provided on each corner of the enclosure for easy placement by a crane. The doors have 3-point pad lockable latching door handles and a recessed penta-head bolt. Rear doors contain tamperproof louvers for ventilation. All doors are equipped with door retainers to secure doors in an open position. Enclosure is marked and labeled in accordance with applicable IEEE and NEMA standards and has a permanently stamped non-corrosive nameplate affixed to the enclosure indicating key equipment data.

Vacuum Switches
Low maintenance, long life,  group operated vacuum switches (oil switches are available upon request) are provided to switch the bank on and off.  The vacuum switches have a 200 amp capacitive switching current rating.


Control Power Transformer
A line-to-ground connected control power transformer is supplied with each bank for internal controls of the capacitor bank (i.e. heaters, convenience outlet, switches, etc.) and power factor, var, and voltage sensing.


Fisher Pierce Meter Socket

Each capacitor bank is equipped with a four or six terminal Meter Socket  for accepting standard socket style capacitor bank controllers for var, temperature, voltage, current, and time controllers.  Many of these controllers can be supplied, pre-wired and configured by NEPSI.

Main Incoming Compartment
Each capacitor bank is equipped with a main incoming "radial feed" dead front compartment for supply termination. ("Feed-through" designs are available on request). The compartment is equipped with ANSI Standard 200 amp bushing wells (600 amp bushing wells are available upon request) and stainless steel parking stands welded to the enclosure wall. A hinged Lexan window is provided for viewing the status of the main incoming fuses.

Capacitors
Each pad-mounted capacitor bank is equipped with group fused all-film low loss (0.07 watt/kvar) double bushing capacitors. The capacitors are manufactured and tested to meet or exceed the requirements of all applicable NEMA and ANSI/IEEE standards.  The dielectric fluid is environmentally friendly, biodegradable, non PCB, and has a low toxicity.  Internal discharge resistors reduce the capacitors residual voltage to less than 50 volts within 5 minutes of de-energization. Capacitors are typically connected in a grounded-wye (ungrounded wye or delta connection can be specified) configuration and are group fused with current limiting fuses. The current limiting fuses are removable through a hinged Lexan window located in the main incoming compartment. The fuses have a 40kA interrupting rating and are equipped with blown fuse indicators. 

Ground Bus
All bus bars, phase and ground, are Tin-plated for maximum conductivity and corrosion resistance. The phase bus is rated for at least 135% of the bank current. The ground bus is provided in both the capacitor compartment as well as the main-incoming compartment through the entire width of the enclosure

Warranty

1-year replacement on the switch and capacitors.



Figure 1
- Typical One Stage Pad-Mounted Capacitor Bank
Showing Location of Isolated Compartments and Bank Features



Optional Accessories

Transient Inrush Reactors
Transient inrush reactors can be supplied reduce the high frequency inrush currents associated with back-to-back capacitor bank switching.  The reactors are rated to carry 135% of the bank's nominal current.  They are epoxy impregnated and consist of Copper Magnet Wire. The reactors are typically purchased when other banks are installed in close proximity.

Surge Arresters
Heavy Duty Distribution Class Lightning Arresters can be provided for transient voltage protection of the capacitor bank.

Thermostatically Controlled Fan
A thermostatically controlled fan can be provided for ambient control of the capacitor bank.

Zero Voltage Capacitor Switching Controls
A zero-voltage closing control can be provided to switch the capacitors on at 0-voltage.  This control will virtually eliminate switching transients associated with capacitor energization.  These controls are recommended when the bank is installed near sensitive loads.

Convenience Outlet
A 15 amp GFI convenience outlet can be provided in the control compartment for local power.

Var, Voltage, Temperature, Current Controller
A Fisher Pierce Series 4400 POWERFLEX AutoCap™ Adaptive Capacitor Bank Controller (contact NEPSI for other types and manufacturers) can be installed in the pad-mounted capacitor bank prior to shipment. This controller will automatically switch the bank based on var, temperature, time, voltage, and current.

Blown Fuse Detection System
Each bank can be equipped with a blown fuse detection system (also known as neutral voltage/current unbalance detection system) that will alert plant personnel of a blown fuse.  It consists of a over voltage/current relay and a neutral voltage/current sensor.  The relay has an adjustable set point to trip or alarm upon detection of a blown fuse.

Enclosure Lights
Enclosure lights can be provided for high visibility during maintenance, and to allow for viewing of fuses through the hinged Lexan window.

Other Options:
Stainless steel or aluminum construction, special finishes, single stage or multi-stage, insulated bus, mimic bus, deadfront or livefront design, air-disconnect switch, hinged compartment barriers, ground switch.

Pad-Mounted Capacitor Bank
Ordering Guide


NEPSI's Pad-Mounted capacitor banks are built in accordance with the standard features listed in the above specification and your specific requirements. Feel free to contact NEPSI for a quote or to discuss your specific application. For budgetary pricing, preliminary dimensions, and weights, proceed to the following web page;

For Voltages or Bank Configurations Not Listed, Contact NEPSI.



Figure 2
- Typical Three-Line Diagram. Ratings, Specific Bank Configuration, and Components are Dependent Upon Voltage Rating and Customer requirements