|
Neutral
Voltage Unbalance
Protection System
Introduction
Ungrounded-wye connected capacitor banks and
harmonic filter banks applied at the medium voltage level should
be equipped with a neutral voltage unbalance protection system.
An unbalance protection system serves two primary functions:
-
It provides over voltage protection to capacitors. These over
voltages are primarily caused by blown fuses and can cause damage
to the capacitors.
- It
provides blown fuse indication.
The
following discussion provides background information on setting
and applying neutral voltage unbalance protection relays on ungrounded-wye
connected capacitor banks and harmonic filter banks. It also serves
as an introduction to NEPSI’s unbalance protection system. Further
information on this topic can be obtained from NEPSI’s technical
staff or in IEEE C37.99-1990, "IEEE Guide for the protection
of Shunt Capacitor Banks".
Background
Shunt capacitor banks and harmonic filter
banks are not typically grounded in industrial and commercial power
systems for a variety of reasons. The main reason for keeping them
ungrounded is to overcome the disadvantages associated with grounded
wye capacitor banks. These disadvantages include:
Due
to these disadvantages, many capacitor banks and harmonic filter
banks are left ungrounded for industrial and commercial power systems
up to 34.5kV. The primary disadvantage of ungrounded banks is the
over voltage that occurs when the bank is unbalanced due to a capacitor
fuse blowing as shown in the Figure 1 below. The over voltage appears
across the remaining capacitors on the phase in which the fuse has
opened. The over voltage can be as high as 50%, depending upon bank
configuration, and can reduce the life and permanently damage the
remaining capacitors. In addition, the kvar output of the bank is
reduced, and can cause the industrial or commercial customer to
be hit with a power factor penalty. For this reason, neutral voltage
unbalance protection should be considered.

Figure
1 - Over
voltage Caused by
capacitor fuse blowing
Neutral
Voltage Unbalance Protection
Considerations
There
are many technical considerations when setting and applying a neutral
voltage unbalance protection system. The following bullets list
the major considerations. They may not all be obtainable for every
bank configuration.
-
The
unbalance protection system should coordinate with the individual
capacitor unit fuses such that the fuses operate to isolate
a defective capacitor unit before the bank is switched out of
service, and thus provide a convenient visual means of locating
the defective capacitor unit.
-
Where
possible, the unbalance protection system should be sensitive
enough to alarm for the loss of one or more capacitors, but
trip out for a loss of sufficient or additional capacitor units
that will cause an over voltage in excess of 110% on the remaining
capacitors.
-
The
unbalance protection system should have a time delay of at least
0.5 seconds to overcome false operations due to inrush, ground
faults on the line, lightning, switching of nearby equipment,
and other transient unbalance conditions.
-
The
unbalance protection system should have a lockout feature to
prevent automatic reclosing of the capacitor bank switching
device.
-
If
the capacitor bank is not equipped with an over voltage relay,
the unbalance protection system should be set with consideration
given to the maximum continuous system operating voltage.
-
To
allow for the effects of inherent unbalance, the unbalance protection
system should be set to alarm at one-half the level of neutral
displacement determined for the desired alarm condition.
-
To
allow for the effects of inherent unbalance, the unbalance protection
system should be set to trip at a level of neutral displacement
that will not cause a capacitor over voltage in excess of the
manufacturer’s recommended maximum continuous operating voltage.
Figure
2 below can help in meeting the above considerations. The figure
shows that a 28% loss in phase kvar can result in a 10% over voltage.
This is the ANSI/IEEE continuous over voltage limit for standard
off-the-shelf shunt capacitors. Other limits are shown for setting
the time-delay requirements on the relay.

Figure
2 -
Graph of Neutral-Ground Voltage and Per Unit Overvoltage for UngroundedCapacitor
and Harmonic Filter Banks with Blown Fuses
NEPSI’s
Neutral Unbalance
Protection System
The figure below shows NEPSI’s neutral unbalance relay
protection scheme designed for ungrounded-wye connected capacitor
banks and harmonic filter banks. The protective scheme consists
of a time delay over voltage relay or meter relay and a neutral
to ground potential sensing device.
The
neutral to ground potential sensing device is actually a resistive
voltage divider and is selected for the lowest voltage ratio attainable,
while still being able to withstand transient and continuous over
voltage conditions in order to obtain the maximum unbalance detection
sensitivity. The device is also rated for full line potential since
it can see full line potential during energization.

Figure
3 -
Typical Neutral Voltage Unbalance Protection
System for a 13.8kV Capacitor Bank
Either
an over voltage relay or over voltage meter relay is available from
NEPSI. Both relays serve the same function. The meter relay, however,
allows the protection engineer the ability to monitor the "ambient"
neutral voltage from inherent unbalances. This allows the relay
to be set above the inherent neutral voltage and will help eliminate
nuisance tripping and alarming. The over voltage meter relay is
equipped with two independent relay outputs that can be set to trip
at different levels. The first level can be set to alarm for a blown
fuse, while the second level can be set to trip the bank off line
for damaging over voltages.
For
more information on the above protection system and other available
from NEPSI, contact NEPSI or the nearest NEPSI sales representative.
Northeast
Power Systems, Inc.
66 Carey Road
Queensbury, New York 12804
Phone: 518-792-4776
Fax: 518-792-5767
E-mail:
sales@nepsi.com
Website: www.nepsi.com
|