Case
Study - Filter Bank Performance & Power Quality Study
This
case study summarizes the results of the power system study that
was conducted by Northeast Power Systems, Inc. (NEPSI) at a facility
in New England. The primary purpose of the study was to test the
performance of an existing 600 kvar 480 volt twelve step automatic
harmonic filter bank and to determine if it was creating power
quality problems within our customers facility..
System
Measurements
Current
and Voltage Distortion measurements were taken at the service
entrance of the facility while the filter bank was energized as
well as de-energized to determine if the filter bank was having
a negative impact on power quality. Table 1 below summarizes
the distortion measurements while the bank was de-energized.

The
Total Harmonic Voltage Distortion (Vthd) reached 1.6% during the
measurement period. The corresponding Total Harmonic Current Distortion
(Ithd) reached 5.4%. The majority of the distortion came from
the 3rd, 5th, and 7th harmonics as shown in Table 1. These recorded
harmonics current values are typical of single phase and three
phase electric furnaces that were present at the site.
Table
2 summarizes the distortion measurements that were recorded while
the filter bank was energized. The total harmonic voltage distortion,
as would be expected, dropped from 1.6% to 1.4% due to the energization
of the harmonic filter. A sizable drop in voltage distortion was
not seen because the majority of voltage distortion present at
the customer site is from the third harmonic where the filter
has very little filtering capability.
Figure
1 provides a comparison chart to help illustrate the performance
of the harmonic filter bank. The filter bank reduced the voltage
harmonics at the 5th, 7th as would be expected.
The increase in voltage distortion at the 4th is also
normal. This increase is due to the resonant point that exists
below the filter bank tuning frequency. The increase in voltage
distortion at the 11th may be a result of load variation
during the measurement period or a resonance on the medium voltage
system from distribution capacitors. The increase, however, is
not of concern.
Figure
1 – Bar Chart Showing Effect of Filter Bank on
System
Voltage Distortion
Figure
2 shows how the current distortion on the service entrance conductors
is effected by the energization of the harmonic filter bank. As
can be seen in the figure, the 5th harmonic current
drops as expected. The increase in the third and forth harmonic
current is normal due to the resonance that exist below the turning
frequency of the harmonic filter bank. The values measured are
within acceptable limits and should not cause any harmonic related
power quality problems at the customer site.
During
testing it was noted that no transient or transient magnification
was occurring during filter bank capacitor stage energization.
In addition, problems at the electric furnaces were not coincident
with the switching of the filter bank stages.
Figure
2 - Bar Chart Showing Effect of Filter Bank on
Current
Distortion at Service Entrance
Filter
Bank Test Results
As
part of the system measurements, NEPSI completely tested the 12
stages of the automatic harmonic filter bank. The following
items were checked.
Table
3 shows the filter bank measurement data taken during the site
visit. Since the capacitor bank is connected in Delta, phase-to-phase
values were measured and are presented in this report. Table 4
provides the phase-to-phase tuning points of each stage as well
as the three-phase kvar, and phase-to-phase kvar of each stage.
Tuning
points above 5.0 in Table 4 are indicated with red text. These
stages (stages 1, 2, 7, & 12) are not tuned correctly due
to capacitor failure (Unlike medium voltage capacitors, low voltage
capacitors lose capacitance over time). It is strongly recommended
that these stages be repaired. The individual capacitors in each
stage can be removed and tested with a digital multi-meter that
measures capacitance. Capacitors with low values will indicate
immanent capacitor failure and should be replaced.
Conclusion
& Recommendation
The
power quality problems that have been occurring with the electric
furnaces do not appear to be a result of any malfunctioning of
the harmonic filter bank. The harmonic filter bank decreases the
system voltage distortion and does not magnify or create in sizable
transients that are of concern. Steady state voltage rise
is also minimal and not of concern.
During
the system measurements, it was seen that a very low amount of
system voltage variation (less than 1/2%) resulted in a sizable
variation in the furnace output. The source of the voltage variation
could not be located, but could be from within the facility or
outside of it (from utility). Due to the small magnitude, however,
the utility would not be responsible for a solution. In regards
to problems associated with the voltage variation, NEPSI recommends
the following:
Continue the search to find the source of voltage variation within
the plant.
Contact your utility and have power quality meters installed at
the service entrance. This metering data may help determine if
the voltage variation is from outside your plant. It is important
to time stamp problems within the plant so that they can be compared
with the measurement data (which also needs to be time stamped).
Change
the control system on the electric furnace to be less responsive
to voltage variations. In addition to the above the following
should be noted.
It is likely that installing line reactors in front of the electric
furnaces will not solve the problems associated with the voltage
variations.
Although transient voltage surge suppression (TVSS) will not solve
the voltage variation problems, they will help protect your equipment
from larger transients associated with lightning, faults, and
switching operations on the utility system, as well as on facilities
power system. The cost of TVSS products are low when the consideration
of loss production and equipment damage are considered.
|
Northeast
Power Systems, Inc.
|
66
Carey Road
Queensbury, New York 12804
|
| Phone:
518-792-4776 |
| Fax:
518-792-5767 |
| E-mail:
sales@nepsi.com |
| Website: www.nepsi.com |