|
Do
Not Mix Standard Shunt Capacitor Banks With Harmonic Filter Banks
Introduction
This
technical note presents the reasons why shunt capacitor banks and
harmonic filter banks should not be applied together on an industrial
or utility power system when a voltage transformation or significant
impedance does not exist between them. Such an application (actually
miss-application) is shown in Figure 1 below. This system
is utilized throughout this technical note to illustrate the problems
that can occur.
Background
Shunt
Capacitor Banks and Harmonic Filter Banks are often applied at the
same voltage level in error for the following reasons.
-
There
is a misconception that the harmonic filter bank will absorb
the harmonic currents away from the capacitor banks and prevent
the harmful effects of harmonic resonance.
-
The
filters are applied to an industrial power system that already
contains shunt capacitor banks. The capacitor banks may
exist on the utility system (as pole-top capacitor banks) or
on individual motors as illustrated in Figure 1. (Key Point
– It is always important to check for existing capacitor banks
before the application of harmonic filter banks).
Figure
1 – Typical
Industrial System Showing Miss-Application of
Harmonic
Filter and Shunt Capacitor Banks
System Description
Harmonic
Analysis – System Impedance Scans
Figure
3 shows and impedance scan for a scenario in which all capacitors
are energized in addition to the harmonic filter bank. The tuning
point, and parallel resonance from the standard capacitors and harmonic
filter bank are illustrated. The following key points should be
noted in regards to Figure 3:
-
The
parallel resonance created by the harmonic filter is not usually
of concern because it occurs at a harmonic order where there
are no harmonic currents being produced by the load. Therefore,
without harmonic current, there will be no harmonic voltage.
This resonant point is stable, and is primarily affected by
the tuning frequency of the filter and short circuit impedance
of the system. It will, however, always remain below the tuning
frequency of the filter.
- The
low impedance created by the 4.7th filter is determined
by the filter and will remain stationary.
- The
parallel resonance created by the standard capacitors is primary
affected by the system short circuit impedance and the amount
of kvar (number of motors in this case) that are on-line at a
given time and the harmonic filter. The resonance will typically
shift around with number of running motors and can create nuisance
problems for industrial plants.

Figure
3 –
Impedance
Scan From Bus #1 Showing Parallel Resonant
Points
Created From the Filter Bank and Standard Capacitors
Figure
4 shows three different impedance scans for scenario 2. The figure
clearly illustrates that the number of motor capacitors dramatically
affects the parallel resonance created by the standard capacitors.
A near 7th system resonance occurs for the case where
there are three motors running. Under Scenario 1, it took only two
motors. It is therefore evident that the filter bank impacts the
performance of standard capacitors. The resulting system, however,
is unacceptable.

Figure
4 –
Impedance Scan From Bus #1 Showing Effects of Motor
Capacitors On System Resonance while a harmonic filter is on-line
Figure
5 shows an impedance scan with just the harmonic filter bank. The
filter bank size has been increased to provide the vars lost by
the motor run capacitors and CAP-1 on Bus-13. As can be seen in
the plot, the impedance to harmonic currents above the tuning frequency
of the filter (4.7th for this filter) is low. The result
will be low harmonic voltages and acceptable system performance.
Key
points about Scenario – 3 are as follows:
-
The
parallel resonance that results from the filter bank will always
remain below the tuning frequency of the filter. For this reason,
filters banks are normally tuned to a frequency below the most
prevalent non-linear load harmonic (i.e. 5th harmonic).
-
The
parallel resonance will shift to the left or right by very small
amounts. The shift is normally caused by a change in system
short circuit impedance, or the size of the filter bank. In
either case, this condition is not normally of concern.
-
The
low impedance part of the scan (tuned frequency of filter at
4.7th harmonic) is determined by the harmonic filter
bank.

Figure
5 – Impedance
Scan From Bus #1 Showing the System Characteristic Impedance
With No Standard Capacitors On-line
Figure
6 shows how the parallel resonant point created by the harmonic
can shift for a change in the short circuit impedance and the number
of motors running (the motors actually change the short circuit
impedance, and therefore changes the resonant location by a small
amount). The plot is only shown for harmonics between the 3rd
and 6th to more clearly illustrate the point. As can
be seen, the parallel resonance only shifts between the 3.8 and
4.2 harmonic.

Figure
6 –
Impedance Scan From Bus #1 Showing Effects on Filter Banks
Parallel Resonance for Varying System Conditions
Harmonic Analysis – Voltage Distortion Calculations
Conclusion
This
Technical Note presented the reasons why standard shunt capacitor
banks and harmonic filter banks should not be applied at the same
voltage level without a significant impedance between them. The
significant impedance may consist of a transformer, or many miles
of distribution line.
If
you are planning on adding a capacitor bank or filter bank to your
power system, it is important to recognize potential application
problems. NEPSI has qualified, experienced, licensed power engineers
that can guide and assist you with the specifics of your application.
|
Northeast
Power Systems, Inc.
|
|
66
Carey Road
Queensbury, New York 12804
|
| Phone:
518-792-4776 |
| Fax:
518-792-5767 |
| E-mail:
sales@nepsi.com |
| Website: www.nepsi.com |
|