|
Checking
Capacitor Banks for
Failed Capacitors
Introduction
This technical note provides background information on capacitance
testing of medium voltage double bushing capacitors commonly
used in capacitor banks and harmonic filter banks with rated
line voltages greater than 2.4kV. Due to their relatively
low capacitance (0.20uF to 100.00uF), testing of the capacitors
can be done with many standard digital multi-meters (DMM's).
Meters such as the Fluke 110, 170, and 180 series can provide
the required data necessary to determine the presence of a
failed capacitor. Although other test methods are available,
such as live testing, this technical note is centered around
testing capacitors in their de-energized state.
Medium
Voltage Capacitors can be internally fused or externally fused.
External fuse operation (as evidenced by a blown fuse indicator
for current limiting fuses, or a "dropped out" fuse
link for expulsion style fuses) may indicate a failed capacitor.
The fuse operation, however, does not guarantee a failed capacitor
as the fuse may have opened due to a faulty fuse or from surges
due to lightning or switching operations. It is therefore
recommended that externally fused capacitors be tested before
replacement in situations where the external fuse has blown.
For internally fused capacitors, testing is required as the
fuse is not visible.
Test Procedure
The following test procedure requires the capacitor/harmonic
filter bank to be grounded and disconnected. Normal high voltage
disconnect, grounding, and test procedures should be followed
and should only be conducted by individuals that are qualified
in the operation and maintenance of medium and high voltage
harmonic filter banks and capacitor banks. A suggested procedure,
but not a necessarily all inclusive procedure is as follows:
-
De-energize the capacitor bank per
the recommendations of the capacitor bank manufacturer.
All necessary safety procedures should be followed.
-
Isolate the capacitor bank (i.e. provide
a visible disconnect) from the medium or high voltage
system.
-
Wait at least five minutes after de-energization
before proceeding to the next step.
-
Ground the capacitor bank. It is important
that each phase as well as the neutral (for ungrounded
banks) be grounded. For banks equipped with vacuum switches,
phase bus grounding should take place on the load side
of the vacuum switches.
-
In addition to the phase bus grounding
and before coming into contact with an individual capacitor,
each capacitor should be individually grounded by touching
its terminals with a grounded tip at the end of a high
voltage stick.
-
Disconnect the line-side terminal
of the capacitor to be tested. This may involve the removal
of a fuse link for externally fused capacitors.
-
After bank grounding, proceed to the
appropriate section below for the type of capacitor.

Figure 1 - Internal Construction
of Externally Fused and Internally
Fused Capacitors of Equal Ratings
Externally Fused and Fuseless
Capacitor Bank Testing
IEEE Std. 18 (IEEE Standard for Shunt Power Capacitors) specifies
the standard ratings of capacitors designed for shunt connection
to alternating current transmission and distribution systems
should have a capacitance rating of 0 to +10% of its nominal
nameplate value. In reality, most manufactures produce capacitors
in the 0 to +2% of its nominal nameplate rating. It is desirable
to detect, remove, and replace open capacitors, shorted capacitors,
and partially failed capacitors. Each of these conditions
can be detected with a DMM as follows:
Shorted Capacitors - Typically the
DMM will show over-load or -O.L- for a completely shorted
capacitor.
Open Capacitors - Typically the DMM
will show a "di.sc" or a very low capacitance reading
(capacitance reading in the 0 to 1 nF).
Partially Failed Capacitors - Typically
the DMM will show a capacitance reading that is more than
10% greater than the capacitors nominal value as shown in
Table-1.
The values listed in Table-1 are for industry
standard shunt capacitors. For double bushing capacitors not
listed in Table-1, a program at the following web address
can be used to calculate the nominal capacitance value based
on nameplate data.
http://www.nepsi.com/cap_calculation.htm
In almost all cases, capacitors utilized
in externally fused capacitor banks and fuseless capacitor
banks will fail in the partially failed condition or the shorted
condition as noted above.
Internally
Fused Capacitor
BankTesting
As with externally fused capacitors, IEEE Std. 18 specifies
capacitance readings in the 0 to +10% range. In reality, internally
fused capacitors will be in the 0 to +2% range. These capacitors
will show signs of failure in the following three ways:
Shorted Capacitors - Typically the
DMM will show over-load or -O.L- for a completely shorted
capacitor.
Open Capacitors - Typically the DMM
will show a "di.sc" or a very low capacitance reading
(capacitance reading in the 0 to 1 nF).
Partially Failed Capacitors - Typically
the DMM will show a capacitance reading that is less than
the capacitors nominal value as shown in Table-1.
It should be noted that internally fused
capacitors are composed of many parallel and series groups
of smaller capacitors called "sections" or "rolls".
Each roll is protected by a fuse element that opens upon roll
failure (See Figure 1). Capacitor manufactures generally recommend
capacitors be removed after the second roll failure. Detection
of this failure can be difficult for the following reasons:
-
The total capacitance loss for a single
roll failure can be as little as 1.5%. A double roll failure
can result in a 3% loss of capacitance.
-
Capacitance over the capacitor operating
temperature range can vary on the order of +/-2% (See
Figure 2).
-
DMM accuracy for capacitance readings
is in the 1% to 2% range.
-
Manufacturer tolerance is typically 1%
to 2%, but can be higher.

Figure 2 - Capacitance Vs. Temperature
for
Film-Foil Capacitors
Due to the above, accurate capacitance records
are required to detect imminent capacitor failure when using
internally fused capacitors.


Northeast
Power Systems, Inc.
66 Carey Road
Queensbury, New York 12804
Phone: 518-792-4776
Fax: 518-792-5767
E-mail:
sales@nepsi.com
Website
: www.nepsi.com
|