|
Cable Selection for Medium Voltage Capacitor
Banks and Harmonic Filter Banks
Introduction
This
document presents the fundamental aspects of cable and conductor
selection for connecting pad mounted shunt capacitor and harmonic
filters to industrial, commercial and utility power systems, with
voltages of 2.4 kV to 34.5 kV.Information on cable selection and
the use of stress cones is provided.The proper selection of these
items can decrease installation time, material cost, and subsequently,
the total installed costs of the capacitor or harmonic filter bank
installation.
Background
Medium and high voltage pad mounted capacitor
banks are most commonly connected to the power system by insulated
cable.For 2400 volt and 4160 volt systems, this cable can be either
shielded or non-shielded.For systems above 4160 volts, the cable
must be shielded in accordance with the requirements of the National
Electric Code (NEC).The termination of shielded cable must be done
with stress relief cones and must be done at all terminating points.
Some
pad mounted capacitor and harmonic filter banks may not require
medium voltage cable if they are supplied with a bushing entry option.For
these banks, bare, or 600 volt conductor may be used.Northeast Power
Systems, Inc. (NEPSI) recommends 600 volt conductor be used,
since the thin, 600 volt layer of insulation will tend to protect
the copper (if copper wire is used) from corrosion.The 600 volt
insulated conductor should be rated for outdoor use and should be
treated as a bare conductor.When installing this conductor, it is
important that the phase-to-phase and phase-to-ground clearance
requirements of the NEC(Table 710-33 of the NEC) be met.The conductors
should also be suitably supported so they can not swing together
from forces due to faults, wind or other acts of nature.
The
choice of 600 volt conductor, for banks with bushing entry, is simple.Determine
the size of conductor from Table 1 and source a conductor rated
for outdoor use.The choice of medium voltage cable, on the other
hand, is a bit more complicated and is the primary topic of this
document.There are a host of options and considerations that cannot
be fully presented, but the major options and considerations are
as follows:
|
Table
1 -Major considerations
|
|
Voltage
and Insulation Level
|
Type of
Insulation
|
|
Type of
Shield
|
Jacket
|
|
Choice
of stress relief cone
|
Conductor
Size
|
An understanding of the above considerations,
may be all that is necessary in choosing the right cable for your
installation.
Voltage and Insulation Level
The Cable should be rated at the
phase-to-phase voltage level of the capacitor or harmonic filter
bank.In addition to the voltage rating, the insulation level of
the cable must be chosen.The cable insulation level is dependent
upon the overcurrent protection and grounding method of the system
at which the bank is being applied.The description of each insulation
level is describe below.A conservative approach, when in doubt,
is to choose the 133% or 173% insulation level.
|
100%
Insulation Level -
|
Cables
in this category should be used on circuits which are provided
with relay protection such that a ground fault condition will
be cleared as quickly as possible, but in any case within
1 minute.This insulation level is applicable to the great
majority of cable installations which are on grounded neutral
systems.
|
|
133%
Insulation Level -
|
Cables
in this category should be used on installations where the
clearing time requirements of the 100% level cannot be met
but there is adequate assurance that the faulted section will
be cleared within one hour.This insulation level may also
be used when greater insulation strength (higher reliability),
than is provided by the 100% level thickness, is desired.
|
|
173%
Insulation Level -
|
This
level is to be used when the time required to de-energize
a faulted section is indefinite, or when the circuit is of
a resonant grounded type.
|
Type
of Insulation
There are a host
of options available when it comes to choosing the type of insulation.The
prominent types in use today include: TRXPLE, XLPE, EPR and HMWPE
insulation.Surveys have indicated that HMWPE cable is seldom used,
while TRXLPE, and EPR insulation seem to be the preferred type.
Shield
Shielded cables are required for voltages
above the 5kV level, and are optional at the 4160 volt and 2400
volt level.The shield controls the electrical stress between the
conductor and ground and it provides protection against water penetrating
into the conductor insulation.Complete cable shielding consist of
two parts:the first is a non-metallic semiconducting layer - either
taped or extruded over the insulation - which totally encloses the
cable, and second, is a metallic conductor of one of several types
which serves to provide a solid bond between the semiconducting
layer and the metallic shield.The metallic shield can take several
forms:i.e. Flat strap concentric neutral, round wire concentric
neutral, wire shield, tape shield and corrugated tape shield.The
choice of shield is primarily dependent upon the fault current carrying
capability of the shield.In general, concentric neutral shields
are not required for capacitor bank applications.Corrugated tape
shield typically have higher fault handling capabilities than tape
and wire shields and are a good choice for capacitor or harmonic
filter bank installations.
Conductor
Ampacity
The conductor ampacity should be chosen
based on the requirements of the NEC.In addition to the NEC requirements,
consideration should be given to future capacitor or harmonic filter
bank expansion, and the added duty requirements from harmonics for
harmonic filter banks.The tables on the last page of this document
show kvar capabilities for different size bare conductors and MV-90
cable at industry standard voltage levels.These tables provide a
conservative conductor sizes that should work for most installations.
The
cable ampacity shown is actually based on the table with the lowest
ampacity rating for high voltage conductors in Tables 310-69 through
310-84.The kvar ratings have 25% derating factor to account for
overvoltages and harmonics.The actual tables and derating factors
of the NEC should be consulted for unusual applications.As much
as a 30%-40% derating factor could apply for elevated ambient temperatures
or unventilated cable tray installations. In addition, for cable
tray installations, a 1/0 or larger conductor is required per the
NEC.
In
general, 5 kV cable is not available in sizes less than #4 AWG and
15kV cable is not available in sizes smaller than #2 AWG.This fact
alone, in many cases, will determine the conductor size requirements.
Jacket
The jacket of medium voltage cable serves
several functions.
|
1
|
Provide
mechanical protection for the cable.
|
|
2
|
Provide
a barrier against ingress of moisture which could harm the
cable insulation or shield material.
|
|
3
|
Provide
some electrical insulation between the shield and ground.This
would become important on cable systems in which only one
side of the shield cable is grounded.
|
|
4
|
For
direct buried cables a semiconducting jacket may provide to
limit the shield to ground voltage.
|
The
choice of jacket mainly lies in the type of application. For applications
involving direct burial, calbe tray, and direct sunlight, the cable
jacket should be marked and listed for the application.
Stress Relief Cones
As discussed above, when shielded conductor
is used, stress relief cones must be used. A stress relief cone
as shown in figure 1, provides a means of reducing and controlling
the electrical stresses where the cable shield system is ended,
just short of the point of termination.

Figure
1 - Typical Stress Relief Cone Shown
Electric Field Grading
There
as three classes of terminations as listed below.
|
Class 1
|
This
class of termination is commonly used outdoors and provides
the following:
|
| |
|
1)
|
Some
form of electric stress control for the cable insulation
shield termination.
|
|
2)
|
Complete
external leakage insulation (sheds to increase creepage
distance) between the medium voltage conductor and ground.
|
|
3)
|
A
seal to prevent the entrance of the external environment
into the cable.
|
|
|
Class
2
|
These
terminations are the same as class one terminations, except
there is no seal (Item 3 in the Class 1 category above) from
the external environment. This type of termination would typically
be used indoor or outdoors when equipped with rain shields
or special outdoor insulation.
|
|
Class
3
|
A
class 3 termination provides electric stress control only
(only the first item in the class 1 category above). This
class of terminations used primarily used indoors.
|
The
termination classes described above are available as pre-molded,
cold shrinkable and heat shrinkable forms.Elastimode, 3M,
Joslyn, and Raycem are major suppliers.Generally, cold shrinkable
are the simplest to install and require no heat.Typically,
an hour is required for each termination. A considerable amount
of time is required to prepare the ends of the cable.
Workmanship in preparing the cable ends is very important.
In addition to the benefits of easy installation, many of
the heat shrinkable and cold shrinkable terminations are as
flexible as the cable they are being placed around. This flexibility
helps in minimizing the required termination clearance. See
NEPSI Technote on cable terminations for further information
on bending
radius and termination clearance.
|
 |
| |
Picture
above shows a 34.5kV Raychem heat shrinkable termination installed
in the incoming compartment of a 10 MVAR 34.5kV Harmonic Filter
Bank.
|
|
Notes
to above tables:
|
|
1
|
Ampacity
based on Table 310-75, 5 kV cable.
|
|
2
|
Ampacity
of cable based on zero shield current (only one side of shield
grounded).
|
|
3
|
Kvar
ratings based on 74% of conductor rating (This is not a requirement
for capacitors above 600 volts, but has been adopted in these
tables to account for voltage rise, harmonics, and manufacturing
tolerances.
|
|
4
|
Where
cable trays are used - Single conductor cable shall be No.
1/0 or larger and shall be of a type listed and marked on
the surface for use in cable tray.Cables may require a derating
of 30% for covered trays.Check Article 318-13 of the NEC for
more detail.
|
|
5
|
Increased
burial depth beyond 36” may require a derating of 6% per increased
foot.Check notes for tables 310-69 through 310-86 of the NEC
for more detail.
|
The
tables and text in this document are for information purposes only,
and Northeast Power Systems or any affiliation thereof, cannot be
held liable for their correctness.
Northeast Power Systems, Inc.
66 Carey Road
Queensbury, New York 12804
Phone: 518-792-4776
Fax:
518-792-5767
E-mail:
sales@nepsi.com
Website:
www.nepsi.com
|