|
Termination
Clearance &
Bending Radius
Introduction
Medium Voltage Capacitor banks and Harmonic
Filter Banks are typically connected to power systems by Type MV-90
shielded power cable. In accordance with manufacturer recommendations
and the NEC (Article 300-34), they shall not be bent to a radius
less than 12 times the diameter for shielded or lead-covered conductors
during or after installation. For multi-conductor or multiplexed
single conductor cables having individually shielded conductors,
the minimum bending radius is 12 times the diameter of the individually
shielded conductors or 7 times the overall diameter, whichever is
greater.
In
consideration of the above constraints, and the fact that the termination
has a length of 9" to 32", it is important that medium
voltage capacitor bank and harmonic filter bank manufacturers provide
enough space for conductor termination. The following can minimize
the required space:
-
Use
of a cable that is appropriately sized for the current rating
of the bank, accounting for future expansion. To large of a
cable will increase the required bending radius and make for
a more difficult installation.
-
Use
of high voltage terminations that are as flexible as the original
cable. Raychem's HVT terminations are an example.
This
document provides background information on bending radius for MV-90
shielded power cable and required termination clearances. NEPSI's
capacitor bank and harmonic filter bank designs are based on meeting
these constraints as well as the above recommendations. Therefore
it is prudent for the installing contractor to follow the recommendations
listed above.
Termination
Clearance
Requirements
The stress control systems of most flexible
terminations provide a linear voltage distribution from the lug
(at high voltage) to the shield termination (at ground potential).
If the termination is installed too close to another termination
or to another phase or grounded metal (enclosure wall), the electric
stress between the terminations or termination and ground will rise
to a level where discharge or flashover may occur. The electric
field stress at the lug is greater than that at the shield end.
The tables below along with the figures provide a guideline as to
the minimum clearances needed between terminations as well as termination
to ground. These clearances are based on IEEE BIL Levels. The table
provides the line-to-line voltage of the system and the BIL. When
choosing the line-to-line voltage in the table, the system voltage
must be equal to or greater than your application voltage.
Table
1 - Minimum Clearance
|
System
Voltage
(KV)
|
BIL
|
A
|
B
|
C
|
D
|
E
|
|
4.76
|
60
|
3.5
|
2.5
|
0.6
|
0.4
|
9.5
|
|
8.25
|
75
|
4.0
|
3.0
|
0.8
|
0.6
|
9.25
|
|
13.8
|
95
|
6.5
|
3.5
|
1.2
|
0.8
|
15
|
|
14.4
|
110
|
7.0
|
4.0
|
1.4
|
0.9
|
15
|
|
23.0
|
125
|
9.0
|
6.0
|
1.6
|
1.0
|
26
|
|
34.5
|
150
|
9.0
|
6.0
|
1.6
|
1.0
|
33
|
|
34.5
|
200
|
13.0
|
9.0
|
2.0
|
1.4
|
33
|
Note:
Values are based on normal operating conditions. Humid or poorly
ventilated environments may require additional air clearance.
Figure 1
- Diagram For Use With Table 1 For
Determining Minimum Clearances
When
installing current transformers on medium voltage cables supplying
capacitor banks and harmonic filter banks it is important that the
shield wire be routed through the current transformer as shown in
figure 1. This allows for proper operation of over current protection
relays.
Recommended Cable
Bending Radius
Many terminations are as flexible as the original
cable. It is recommended that these types of terminations be utilized
when installing NEPSI's harmonic filter banks and capacitor banks.
When used, the cable end should not be bent to a radius less than
that recommended by the manufacturer or 12 times the cable diameter
as required by the NEC (which ever is smaller). The figure below
provides a guideline as to the bending radius in a typical installation.
"D" in the figure is equal to the cable jacket diameter
for a single-conductor cable or tubing-diameter for a three-conductor
cable. In general the minimum bending radius for a single-conductor
cable and multi-conductor cable with and overall shield is twelve
times the overall singe cable diameter or seven times the overall
tubing diameter. The tables below show typical diameters for shielded
single conductor, 133% insulation level, XLP cable. The voltage
for each class of cable is provided. From the tables, the minimum
bending radius can be calculated. These tables are only to be used
as a guideline since different manufactures have different dimensions
and requirements. For specific information on the bending radius,
the cable manufacturer should be consulted.
Table 2 - Typical
Cable Characteristics
|
5000
Volt 133% Insulation Cable
|
|
15000
Volt 133% Insulation Cable
|
|
Size
AWG or Kcmil
|
Nominal
Diameter Inches
|
*
Ampacity Conduit
|
|
Size
AWG or Kcmil
|
Nominal
Diameter Inches
|
*
Ampacity Conduit
|
|
8
|
0.56
|
55
|
|
-
|
-
|
-
|
|
6
|
0.60
|
75
|
|
-
|
-
|
-
|
|
4
|
0.65
|
97
|
|
-
|
-
|
-
|
|
2
|
0.70
|
130
|
|
2
|
1.05
|
150
|
|
1
|
0.74
|
155
|
|
1
|
1.09
|
170
|
|
1/0
|
0.78
|
180
|
|
1/0
|
1.13
|
195
|
|
2/0
|
0.87
|
205
|
|
2/0
|
1.17
|
225
|
|
3/0
|
0.92
|
240
|
|
3/0
|
1.22
|
260
|
|
4/0
|
0.98
|
280
|
|
4/0
|
1.28
|
295
|
|
250
|
1.02
|
315
|
|
250
|
1.34
|
330
|
|
350
|
1.12
|
385
|
|
350
|
1.44
|
395
|
|
500
|
1.25
|
475
|
|
500
|
1.57
|
480
|
|
750
|
1.44
|
600
|
|
750
|
1.82
|
585
|
|
1000
|
1.58
|
690
|
|
1000
|
1.93
|
675
|
|
25000
Volt 133% Insulation Cable
|
|
25000
Volt 133% Insulation Cable
|
|
Size
AWG or Kcmil
|
Nominal
Diameter
Inches
|
*
Ampacity
Conduit
|
|
Size
AWG or Kcmil
|
Nominal
Diameter Inches
|
*
Ampacity Conduit
|
|
1
|
1.34
|
170
|
|
-
|
-
|
-
|
|
1/0
|
1.39
|
195
|
|
1/0
|
1.60
|
195
|
|
2/0
|
1.44
|
225
|
|
2/0
|
1.64
|
225
|
|
3/0
|
1.49
|
260
|
|
3/0
|
1.68
|
260
|
|
4/0
|
1.53
|
295
|
|
4/0
|
1.70
|
295
|
|
250
|
1.59
|
330
|
|
250
|
1.81
|
330
|
|
350
|
1.69
|
395
|
|
350
|
1.93
|
395
|
|
500
|
1.90
|
480
|
|
500
|
2.06
|
480
|
|
750
|
2.09
|
585
|
|
750
|
2.24
|
585
|
|
1000
|
2.24
|
675
|
|
1000
|
2.40
|
675
|
Note:
The
Ampacity is based on three cable in isolated conduit in air, 90
deg. C conductor temperature, 40 deg. C. Ambient. For other installation
conditions, refer to the National Electrical Code. Please note that
the NEC requires that the conductors feeding a capacitor bank must
have a rating of at least 135% of the ampacity rating of the capacitor
bank.
Conclusion
NEPSI's capacitor banks and harmonic filter
banks are designed with adequate clearance for incoming power cables.
The clearances are based on the use of appropriately sized cables
and flexible cable terminations. When flexible terminations are
not going to be used, or when a much higher ampacity cable is going
be utilized, NEPSI should be notified. This will guarantee a trouble
free, hassle free installation.
Northeast
Power Systems, Inc.
66
Carey Road
Queensbury,
New York 12804
Phone:
518-792-4776
Fax:
518-792-5767
E-mail:
sales@nepsi.com
Website: www.nepsi.com
|